HCS_0001_Hygienic Component Solutions Catalog_Rev7.0 (2024)

Cv Values & Pressure Drops for Y-Strainers Cv values or the provided pressure drop tables can be used to estimate the pressure drop across a strainer at a given flow rate. Cv values are for water at 70 °F. Contact Sani-Matic for inquiries on pressure drops for fluids with other viscosities.

Strainer Body Size

Connection Size

Cv

1.5"

39

2.0"

75

4.0"

2.5"

109

3.0"

138

6.0"

4.0"

248

Y-Strainer Pressure Drop: 4.0" Body

Y-Strainer Pressure Drop: 6.0" Body

NOTE: Cv values and charted pressure drops can be used for perforated, wedgewire, and perforated with mesh overlays or filter tubes. The clean pressure drop is minimally impacted by the element configuration in most cases. For worst-case calculations, add 20% to the calculated pressure drop.

65

HCS-0001.7