d. PLC Network Settings
Note (1)
Note (2)
Note (3)
Notes If the DPR is to communicate with another PLC (Allen-Bradley ControlLogix or CompactLogix) for virtual I/O data collection, the Micro800 PLC in the DPR panel will have to be able to communicate over Ethernet to that PLC. The Micro800 PLC comes configured with default IP address settings that can be changed if needed using the HMI screen. 1. Press the IP address, mask, or default gateway text boxes to bring up the on-screen keyboard to modify any of the values. 2. Press the “Use Optix Serial PLC Driver” to enable or disable serial communication to the Micro800 PLC. The communication protocol defaults to a serial connection; however, an Ethernet connection can be used if preferred. If using an Ethernet connection, the Ethernet driver address MUST be specified. This will be the same IP address as the Micro800. Using the Ethernet driver REQUIRES BOTH the DPR HMI panel AND the Micro800 PLC to be on the same subnet. 3. Press the “Apply” button to apply any of the PLC network changes. After changing any of the PLC network settings, the PLC must be power cycled, not just the DPR HMI panel. This can be done by cycling power to the DPR control panel, or by cycling the main circuit breaker within the DPR control panel.
DM-0013_Digital Process Recorder (DPR)_IOM_Rev4.0
22 of 76
Powered by FlippingBook